Thermo EIE

Note: If your Flow Automation devices use native messaging, use the Flow Automation EIE instead of the Thermo EIE.

The Thermo EIE supports Modbus protocol functionality for AutoMATE, AutoPILOT, AutoPILOT PRO, and AutoEXEC devices. It supports a special Modbus protocol for SuperFlo II devices. Like the Modbus EFM EIE, the Thermo EIE supports Enron data groups. AutoMATE, AutoPILOT, AutoPILOT PRO, and AutoEXEC templates can be altered for all supported devices. However, SuperFlo II data groups and data group elements cannot be altered; only minor alterations can be made to the SuperFlo II template (for instance, to default UDC mappings).

Some of the features of the Thermo EIE are cryout support, user-configurable data groups, support for multiple communication formats (RTU, TCP/IP, and ASCII), and dynamic single-register data groups. The SuperFlo II only supports the RTU Modbus communication format.

Specifications

The following table lists and describes EIE specifications.

Manufacturer

Thermo Scientific

Protocol(s)

Modbus

Special SuperFlo II Modbus

Model(s)

Thermo AutoEXEC

Thermo AutoMATE

Thermo AutoPILOT

Thermo AutoPILOT PRO

Thermo SuperFlo II

Flow Automation SuperFlo II

Required Files

CxDdsThermoEditors.dll

UisThermoDeviceDriver.dll or UisThermoDeviceDriver64.dll

Sample Templates

Thermo_AutoPilotAutoMate.dtf

Thermo_AutoPilotProExec.dtf

eieType

Thermo

Cryout Support

Yes

FMS Support

Yes for AutoPILOT, AutoMATE, AutoPILOT PRO, and AutoEXEC, using FMS EFM data items.

No for SuperFlo II.

Note: In cases where both GMR and FMS support was previously available, CygNet Measurement now provides data support using FMS data items only. If you were previously using GMR data items, you must update to use FMS data items. Update options are provided as part of your software upgrade procedure.

Listen Mode

No for SuperFlo II

Yes for AutoPILOT, AutoMATE, AutoPILOT PRO, and AutoEXEC

64-bit Support

Yes. See 64-bit Device Drivers.

For more information, see sample device template files and manufacturer documentation.